Technical guide
VFD Ground Fault Troubleshooting and Motor Insulation Check
Isolate a VFD ground fault or earth fault by checking drive current sensors, disconnecting motor leads for a megger test, and limiting cable length.

Jack Dean writes practical VFD selection, wiring, replacement and power-quality guides using current manufacturer documentation and explicit procurement checks.
Author profileStart your VFD ground fault or VFD earth fault troubleshooting workflow by recording the active keypad fault entry before resetting the drive, then isolating the motor cable from the drive output terminals before performing a motor megger test VFD check. Use the manufacturer parameter references, insulation resistance test voltages, and cable capacitance rules in this VFD Learning Center guide to separate a true phase-to-ground insulation failure from a non-running sensor false alarm or high-frequency leakage trip. Pair your recorded trip log from our VFD fault log before reset guide with your disconnected megger readings when preparing a variable frequency drives enquiry.
How a VFD detects a ground fault or earth fault and what causes false alarms
Compare how internal drive current sensors, control parameters, and fault codes monitor phase-to-ground leakage across ABB, Danfoss, Rockwell Automation, and Yaskawa drives:
The ABB ACS580-01 drive is equipped with an internal ground fault protective function to protect the unit against ground faults in the motor and motor cable; this function is not a personnel safety or a fire protection feature.
On ABB ACS580 Standard Control Program, parameter 31.20 Earth fault (default Fault) selects how the drive reacts when an earth (ground) fault or current unbalance is detected in the motor or the motor cable: 0 = No action, 1 = Warning (generates an A2B3 Earth leakage warning), and 2 = Fault (the drive trips on fault 2330 Earth leakage).
On ABB ACS580 Standard Control Program, warning A2B3 Earth leakage indicates the drive has detected load unbalance typically due to earth fault in motor or motor cable; corrective actions are to check there are no power factor correction capacitors or surge absorbers in the motor cable, and check for an earth fault in the motor or motor cables by measuring the insulation resistances of the motor and motor cable.
On ABB ACS580 Standard Control Program, fault 2330 Earth leakage indicates the drive has detected load unbalance typically due to earth fault in motor or motor cable; corrective actions are to check there are no power factor correction capacitors or surge absorbers in the motor cable, check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable, and try running the motor in scalar control mode if allowed (parameter 99.04 Motor control mode).
On ABB ACS550-01/U1 drives, parameter 3017 EARTH FAULT defines the drive response if the drive detects a ground fault in the motor or motor cables while running and while not running: 0 = DISABLE (no drive response to ground faults) and 1 = ENABLE (ground faults display fault 16 EARTH FAULT, and if running the drive coasts to stop); disabling earth fault (ground fault) may void the warranty.
On ABB ACS550-01/U1 drives, parameter 3023 WIRING FAULT defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running: it monitors for improper connections of input power to the drive output (fault 35, OUTPUT WIRING) and ground faults (fault 16, EARTH FAULT), with settings 0 = DISABLE and 1 = ENABLE.
On ABB ACS550-01/U1 drives, parameter 3028 EARTH FAULT LVL defines the detection level for earth fault (when parameter 3017 EARTH FAULT is enabled): 1 = LOW (low level leakage current, high sensitivity, default in the USA software version), 2 = MEDIUM (medium sensitivity to ground fault current, default in the European software version), and 3 = HIGH (high level leakage current, low sensitivity).
On ABB ACS550-01/U1 drives, fault 16 EARTH FAULT indicates a possible ground fault detected in the motor or motor cables; detection is more sensitive when the drive is not running and can produce false positives, and a delta grounded input power supply and motor cables with high capacitance may result in erroneous error reports during non-running tests.
On ABB ACS355 drives, Earth fault protection detects earth faults in the motor or motor cable (an earth fault in the input power line does not activate the protection), and parameter 3017 EARTH FAULT selects DISABLE (0, No action), ENABLE (1, trips on fault EARTH FAULT 0016 when the earth fault is detected during run), or START ONLY (2, trips on fault EARTH FAULT 0016 when the earth fault is detected before run).
On ABB ACS355 drives, fault 0016 EARTH FAULT (2330) indicates the drive has detected an earth (ground) fault in the motor or motor cable, or a drive internal fault; an internal short-circuit may cause earth fault indication, which has happened if fault 0001 appears after disabling the earth fault, in which case replace the drive.
In the Danfoss VLT AutomationDrive FC 301/FC 302 Programming Guide, ALARM 14, Earth (Ground) Fault occurs when there is current from the output phase to ground in the cable between the drive and the motor or in the motor itself; the current sensors detect the ground fault by measuring current going out from the drive and current going into the drive from the motor (issued if the deviation of the 2 currents is too large), and troubleshooting includes removing power to repair the ground fault, measuring the resistance to ground of the motor cables and the motor with a megohmmeter, and resetting any potential individual offset in the 3 current sensors in the drive by performing a manual initialization or a complete AMA (most relevant after changing the power card).
In the Danfoss VLT AutomationDrive FC 301/FC 302 Programming Guide, ALARM 45, Earth (Ground) Fault 2 indicates a ground fault has occurred; troubleshooting steps are to check for proper grounding and loose connections, check for proper wire size, and check the motor cables for short circuits or leakage currents.
In the Danfoss VLT AutomationDrive FC 360 Programming Guide, for parameter 14-90 Fault Level, only for drive of power size 30–75 kW (40–100 hp), if [0] Off is selected, the earth fault protection is disabled only for the earth fault which happens during running and when the short-circuit current to ground is lower than 200%; disabling the ground fault may damage the drive and void the warranty.
On Rockwell Automation PowerFlex 40P drives, Fault F13 Ground Fault indicates a current path to earth ground has been detected at one or more of the drive output terminals (action: check the motor and external wiring to the drive output terminals for a grounded condition), and the drive specifications define Overcurrent as 200% hardware limit and 300% instantaneous fault, Ground Fault Trip as Phase-to-ground on drive output, and Short Circuit Trip as Phase-to-phase on drive output.
In the Yaskawa G5 Modbus Plus Technical Manual, Short Circuit displays code SC (hexadecimal code 5, Major Fault M), Ground Fault displays code GF (hexadecimal code 6, Major Fault M), and Overcurrent displays code oC (hexadecimal code 7, Major Fault M).
On Yaskawa GA800 drives, the access level for parameters L8-09 (Output Ground Fault Detection), L8-15 (oL2 Characteristics Sel atLowSpd), L8-18 (Software Current Limit Selection), and L8-38 (Carrier Frequency Reduction) was changed to expert.
If the recorded keypad code points to a phase-to-phase or load overcurrent event instead of a phase-to-ground fault, continue with our VFD overcurrent fault diagnostic record.
Why megger testing a connected VFD is prohibited and how to isolate the motor cable
Follow these manufacturer isolation rules before connecting an insulation resistance tester to any motor cable or braking resistor:
On ABB ACS580-01 drives, do not do any voltage withstand or insulation resistance tests on any part of the drive as testing can damage the drive; every drive has been tested for insulation between the main circuit and the chassis at the factory, and voltage-limiting circuits inside the drive cut down the testing voltage automatically.
On ABB ACS550-01/U1 drives, do not make any voltage tolerance or insulation resistance tests on any part of the drive as testing can damage the drive; every drive has been tested for insulation between the main circuit and the chassis at the factory, and voltage-limiting circuits inside the drive cut down the testing voltage automatically.
On ABB ACS355 drives, do not make any voltage tolerance or insulation resistance tests (for example hi-pot or megger) on any part of the drive as testing can damage the drive.
On ABB ACS580-01 drives, before measuring the insulation resistance of the motor and motor cable, do the steps in section Electrical safety precautions (page 22) and make sure that the motor cable is disconnected from the drive output terminals.
On ABB ACS580-01 drives, for the brake resistor assembly for frames R1…R3, make sure that the resistor cable is connected to the resistor and disconnected from the drive output terminals, connect the R+ and R- conductors of the resistor cable together at the drive end, and measure the insulation resistance between the conductors and the PE conductor with a measuring voltage of 1000 V DC; the insulation resistance must be more than 1 Mohm.
Disconnect the motor cable conductors completely from the drive output terminals before applying any test voltage.

Disconnect the motor cable phase conductors from the drive output terminals before performing any insulation resistance measurement.
Motor megger test VFD voltages, resistance thresholds, and discharge rules
Verify the required DC test voltage, reference temperature, absorption ratios, and post-test discharge duration for the motor and cable:
On ABB ACS580-01 drives, measure the insulation resistance between each phase conductor and the protective earth conductor using a measuring voltage of 1000 V DC; the insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 °C [77 °F]), and for other motors refer to the manufacturer’s instructions.
On ABB ACS580-01 drives, moisture inside the motor reduces the insulation resistance; if you think that there is moisture in the motor, dry the motor and do the measurement again.
On ABB ACS550-01/U1 drives, check that the motor cable is connected to the motor and disconnected from the drive output terminals U2, V2 and W2, then measure the insulation resistance between phase conductors and between each phase conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC; the insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F).
On ABB ACS355 drives, check that the motor cable is connected to the motor and disconnected from the drive output terminals U2, V2 and W2, and measure the insulation resistance between each phase conductor and the Protective Earth conductor using a measuring voltage of 500 V DC; the insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F).
In Megger's A Stitch in Time guide, commonly used DC test voltages for routine maintenance by equipment AC rating are: up to 100 volts uses 100 and 250 volts; 440 to 550 volts uses 500 and 1,000 volts; 2,400 volts uses 1,000 to 2,500 volts or higher; and 4,160 volts and above uses 1,000 to 5,000 volts, or higher.
In Megger's A Stitch in Time guide, in the Short-Time or Spot-Reading Test method, you connect the Megger instrument across the insulation to be tested and operate it for a short, specific time period (60 seconds is usually recommended); quite often the value would be less for 30 seconds, more for 60 seconds.
In Table I (Condition of Insulation Indicated by Dielectric Absorption Ratios) of Megger's A Stitch in Time guide, for the 60/30-Second Ratio, 1.0 to 1.25 indicates Questionable, 1.4 to 1.6 indicates Good, and Above 1.6 indicates Excellent; for the 10/1-Minute Ratio (Polarization Index), Less than 1 indicates Dangerous, 1.0 to 2 indicates Questionable, 2 to 4 indicates Good, and Above 4 indicates Excellent.
As quoted in Megger's A Stitch in Time guide, the IEEE guide 'Recommended Practices for Testing Insulation Resistance of Rotating Machinery' states that the recommended minimum insulation resistance Rm for alternating-current and direct-current machine armature windings and for field windings of alternating-current and direct-current machines can be determined by Rm = kV + 1, where Rm is the recommended minimum insulation resistance in megohms at 40°C of the entire machine winding and kV is the rated machine terminal to terminal potential in kilovolts.
In Megger's A Stitch in Time guide, under the temperature thumb rule for insulation resistance, for every 10°C increase in temperature, halve the resistance, or for every 10°C decrease, double the resistance; for example, a two-megohm resistance at 20°C reduces to 1/2 megohm at 40°C.
In Megger's A Stitch in Time guide, absorption current decreases at a relatively slow rate and its stored energy must be released at the end of a test, requiring a longer time than the capacitance charging current—about four times as long as the voltage was applied; do not disconnect the test leads for at least 30 to 60 seconds following a test, allowing time for capacitance discharge.
In Southwire Cable Tech Support guidance on insulation resistance testing, insulation resistance testing is a non-destructive test procedure that measures the insulation resistance between the phases and/or between phase and ground; for single conductor non-shielded cable on a reel, insulation resistance testing cannot be performed because low voltage single conductors do not have a grounding conductor, shield or ground plane, and for other cable on a reel, sealing caps must be removed from both ends because residue inside the sealing cap can be conductive and lead to false readings.
If disconnecting the cable at the motor terminal box shows that the stator winding insulation itself has failed, review our inverter duty motor insulation and bearing current guide and include the motor nameplate data in your industrial motors enquiry.

Measure insulation resistance between each disconnected phase conductor and the protective earth conductor, then leave the leads connected to discharge stored energy.
Suppress long-cable capacitance, common-mode leakage, and nuisance RCD trips
When the motor and cable pass insulation resistance checks but the drive or upstream residual current device still trips, check how cable capacitance, output filters, shield bonding, and RCD selection interact:
In KEB America guidance on ground fault nuisance tripping in VFD applications, current flow through capacitive coupling between current-carrying conductors and grounded elements (metal conduits, motor frames, machine cabinets) is exacerbated because a capacitor's impedance to current flow is inversely proportional to the frequency of the current flowing through it, so higher frequency currents caused by fast switching semiconductors more easily flow through capacitive couplings to ground; KEB notes drive decoupling X and Y capacitors: Y-capacitors are designed to fail as an open circuit (making them ideal for decoupling power phases to ground), whereas X-capacitors are designed to fail as a closed-circuit shorting two phases causing an overcurrent fault.
In Section 7.1 (Cable Capacitance Effects) of the GAMBICA / BEAMA Technical Guide, at each inverter output pulse the distributed cable capacitance (C1 - Cn in Figure 3) must be charged and discharged; for small motors with 'long' cables, the cable charging currents may be of the same order as the motor rated current, and cable charging currents may cause nuisance inverter overcurrent tripping, with maximum cable length recommendations varying from 10 m on very small drives to above 250 m on high power drives.
In Section 6.2 (Output Reactors) of the GAMBICA / BEAMA Technical Guide, in the Figure 22 example (comparing to the 42 m case in Figure 9), the addition of the output reactor extended the rise time to around 5 µs and reduced the peak voltage to 792 V, with reduced efficiency of less than approx. 0.5%; output reactors can also be used to compensate for cable charging currents (balances cable capacitance) and may be used for motor cable lengths up to many hundred metres on larger drives.
In Section 6.3 (Voltage Limiting Filter / dv/dt Filter) of the GAMBICA / BEAMA Technical Guide, a design consisting of capacitors, inductors and diodes or resistors may be used to limit the dv/dt to typically less than 500 V/µs (in the Figure 23 example, the peak voltage is reduced to 684 V with a dv/dt of 40 V/µs), and increased losses of 0.5 - 1.0% must be accommodated.
On Schneider Electric Altivar Machine ATV320 drives, only use cables with insulator heat resistance of 75°C (167°F) min; if using cables longer than 50 m (164 ft) between the drive and the motor, add output filters; use a shielded cable to meet Category C2 or C3 according to IEC 61800-3; to limit currents in common mode, use common mode output filters (ferrite) to reduce circulating currents in the motor windings; and use of cables with lower linear capacity could increase cable length performances.
On Schneider Electric Altivar Machine ATV320 drives, the product has a leakage current greater than 3.5 mA, equipment grounding must ensure that the resistance to Ground is 1 Ohm or less, and installers must not use conduits as protective ground conductors (use a protective ground conductor inside the conduit) and must not consider cable shields to be protective ground conductors.
On Schneider Electric Altivar Machine ATV320 drives, use a Type A or Type F Residual Current Device (RCD / GFCI) or Residual Current Monitor (RCM) for single-phase devices connected to a phase and to the neutral conductor, and use a Type B RCD / GFCI or RCM approved for use with frequency inverters for three-phase devices; due to high leakage current in standard operation, Schneider Electric recommends choosing at least a 300 mA device integrating high-frequency current filtering and a time delay (the time delay is not available for a 30 mA device), and providing one residual current device per drive when the installation includes several drives.
On ABB ACS580-01 drives, the drive is suitable to be used with residual current devices of Type B; as standard, the drive contains capacitors connected between the main circuit and the frame, and these capacitors and long motor cables increase the ground leakage current and may cause nuisance faults in residual current devices.
On ABB ACS580-01 drives, for minimum radio-frequency interference, ground the motor cable shield 360 degrees at the cable entry of the motor terminal box, and the drive switching frequency settings are 2 kHz, 4 kHz (default), 8 kHz, and 12 kHz.
On Rockwell Automation PowerFlex 40P drives, if a system ground fault monitor (RCD) is to be used, only Type B (adjustable) devices should be used to avoid nuisance tripping.
Use our VFD motor cable length checklist to document the installed run and compare output reactors, voltage-limiting filters, and common-mode ferrite cores in our power quality products catalog.

Bond the motor cable shield around the terminal box entry and use output reactors or common-mode ferrite cores where long runs increase capacitive leakage.
Prepare your VFD ground fault and insulation check enquiry
When you request a replacement variable frequency drive, industrial motor, or output filter quotation after troubleshooting a ground fault, include the details below:
| Enquiry item | Details to include |
|---|---|
| Fault code and trip state | Provide the displayed ground fault or earth fault code and state whether the trip occurred before starting or during running. |
| Drive and supply details | Provide the drive part number, supply earthing arrangement, switching frequency setting, and upstream residual current device type. |
| Megger test readings | Provide the disconnected motor and cable insulation resistance readings, the applied DC test voltage, and the winding temperature. |
| Cable route and shielding | Provide the installed motor cable length, conductor insulation type, and shield grounding arrangement at both ends. |
| Output filtering and motor data | Provide the motor nameplate details and note any existing output reactor, voltage-limiting filter, or common-mode ferrite core. |
Swipe or scroll horizontally to see all columns.
Discuss your variable frequency drives, power quality products, or industrial motors sourcing requirements with us. Send your recorded fault code, disconnected megger readings, cable length, and nameplate data via WhatsApp or our contact page.
Frequently asked questions
Can you perform a megger or hi-pot insulation test directly on a VFD?
No. Never apply a megger or hi-pot tester to variable frequency drive terminals—drives are factory insulation-tested, and internal voltage-limiting components will clamp the test voltage and suffer permanent damage. Always disconnect the motor leads from the drive output first.
What megger test voltage and minimum resistance apply to an ABB motor on an ACS580-01 vs an ACS355 drive?
With the motor cable disconnected from the drive output terminals (U2, V2, W2), ABB specifies testing phase-to-PE insulation at 1000 V DC for ACS580-01/ACS550-01 installations and 500 V DC for ACS355 installations; in both cases, an ABB motor must measure above 100 MOhm at 25 °C (77 °F).
Why can a Danfoss VLT AutomationDrive report an earth fault after a power card replacement?
Danfoss FC 301/FC 302 drives trigger Alarm 14 when the sum of outgoing and returning phase currents deviates beyond threshold. After verifying motor and cable insulation with a megohmmeter, run a manual initialization or complete Automatic Motor Adaptation (AMA) to zero out any individual current-sensor offset introduced when replacing the power card.
What type of upstream RCD or GFCI is used with three-phase variable frequency drives?
Three-phase VFDs require a Type B residual current device (RCD/GFCI or RCM) approved for frequency inverters, whereas single-phase phase-to-neutral drives use Type A or Type F. For three-phase Altivar ATV320 installations, Schneider Electric specifies at least a 300 mA Type B unit with high-frequency filtering, a time delay, and dedicated one-RCD-per-drive protection.
What information should be included when requesting a replacement VFD or output filter quote after a ground fault?
Include the recorded ground fault code, drive and motor nameplate data, disconnected motor and cable megger readings with winding temperature, and the installed motor cable length via WhatsApp or our contact page.
Sources
- ABB — General Purpose Drives Hardware Manual
- ABB — Control Program Firmware Manual
- ABB — Variable Frequency Drives User Manual
- ABB — Machinery Drives User Manual
- Danfoss — VLT AutomationDrive FC 301/FC 302 Programming Guide
- Danfoss — VLT AutomationDrive FC 360 Programming Guide
- Rockwell Automation — Adjustable Frequency AC Drive User Manual
- Yaskawa — AC Drive Technical Manual
- Schneider Electric — Altivar Machine Installation Manual
- GAMBICA and BEAMA — Variable Speed Drives and Motors Technical Guide
- Megger — Complete Guide to Electrical Insulation Testing
- Southwire — Cable Tech Support Insulation Resistance Testing Guide
- KEB America — Ground Fault Nuisance Tripping in VFD Applications