Technical guide
VFD Troubleshooting: Fault Log before Reset
Record active VFD fault codes, DC bus voltage, output current, and status words from the drive trip log before pressing Reset or cycling power.

Jack Dean writes practical VFD selection, wiring, replacement and power-quality guides using current manufacturer documentation and explicit procurement checks.
Author profileStart your VFD troubleshooting workflow by reading the active fault code, operating snapshot, and fault history on the keypad before pressing Reset or cycling power. Use the ABB, Yaskawa, and Danfoss parameter references below to record the frozen motor speed, output frequency, intermediate circuit voltage, motor current, and status word while the drive remains in its stopped state. Bring the captured fault log and motor nameplate details to your variable frequency drives enquiry.
Why the live status screen and power cycling erase diagnostic context
Compare what happens to the drive output, live display, and stored fault details when an error occurs or when cabinet power is cycled:
When an error or fault happens on a VFD, the drive typically stops modulation, which is the rapid on/off switching of output voltage.
On Danfoss VLT AutomationDrive, when a Trip occurs (such as Earth Fault [A14] Auto Remote Trip), the live Status screen displays 0.0Hz, 0.00A, and 0.000kW.
In ABB ACS550-01/U1 Fault Logger mode, the user can view the drive fault history of maximum ten faults, and after a power off, only the three latest faults are kept in the memory.
In ABB ACS550-01/U1 Fault Logger mode, the user can see the details of the three latest faults, and after a power off, the details of only the most recent fault is kept in the memory.
On ABB ACS580 Standard Control Program, informative event 64FF Fault reset is logged when a fault has been reset from the control panel, Drive composer PC tool, fieldbus, or I/O.
Copy the active fault display and the frozen operating values onto your troubleshooting sheet before clearing the fault or opening the supply disconnect. If the drive stopped on an overcurrent event, pair this log with our VFD overcurrent fault diagnostic record, or if it stopped on an earth fault, continue with our VFD ground fault troubleshooting and insulation check guide.

Record the active fault entry and frozen operating values from the keypad before pressing Reset.
Read the ABB fault history and operating snapshot parameters
For the ABB assistant control panel and fault history parameter group:
On ABB ACS550-01/U1, the last three fault codes are stored into parameters 0401, 0412, and 0413, while additional data is stored in parameters 0402…0411 for the most recent fault identified by parameter 0401.
On ABB ACS550-01/U1, parameter 0401 LAST FAULT displays NO RECORD when set to 0, which clears the fault history, or displays the fault code of the last recorded fault as a name.
On ABB ACS550-01/U1, parameter 0403 FAULT TIME 2 records the time at which the last fault occurred (in format hh:mm:ss when the real time clock is operating).
On ABB ACS550-01/U1, parameter 0404 SPEED AT FLT records the motor speed (rpm) and parameter 0405 FREQ AT FLT records the frequency (Hz) at the time the last fault occurred.
On ABB ACS550-01/U1, parameter 0406 VOLTAGE AT FLT records the DC bus voltage (V) and parameter 0407 CURRENT AT FLT records the motor current (A) at the time the last fault occurred.
On ABB ACS550-01/U1, parameter 0408 TORQUE AT FLT records motor torque (%) and parameter 0409 STATUS AT FLT records drive status (hex code word) at the time the last fault occurred.
On ABB ACS550-01/U1, parameter 0410 DI 1-3 AT FLT records the status of digital inputs 1…3 and parameter 0411 DI 4-6 AT FLT records the status of digital inputs 4…6 at the time the last fault occurred.
On ABB ACS550-01/U1, read-only parameter 0412 PREVIOUS FAULT 1 stores the fault code of the second last fault, and read-only parameter 0413 PREVIOUS FAULT 2 stores the fault code of the third last fault.
On ABB ACS550-01/U1, faults indicated by a flashing red LED are reset by turning the power off for 5 minutes, whereas faults indicated by a non-flashing red LED are reset after correcting the problem and then pressing RESET from the control panel (or turning the power off for 5 minutes).
For the ABB machinery drive fault history parameter group:
On ABB ACS355, parameter group 04 FAULT HISTORY is read-only; parameter 0401 LAST FAULT stores the code of the latest fault (1 = 1), where 0 indicates the fault history is clear.
On ABB ACS355, parameter 0404 SPEED AT FLT records motor speed in rpm (1 = 1 rpm) and parameter 0405 FREQ AT FLT records frequency in Hz (1 = 0.1 Hz) at the time the latest fault occurred.
On ABB ACS355, parameter 0406 VOLTAGE AT FLT records intermediate circuit voltage in V DC (1 = 0.1 V) and parameter 0407 CURRENT AT FLT records motor current in A (1 = 0.1 A) at the time the latest fault occurred.
On ABB ACS355, parameter 0408 TORQUE AT FLT records motor torque as a percentage of motor nominal torque (1 = 0.1%) and 0409 STATUS AT FLT records drive status in hexadecimal format at the time the latest fault occurred.
On ABB ACS355, parameter 0412 PREVIOUS FAULT 1 stores the fault code of the 2nd latest fault (1=1) and parameter 0413 PREVIOUS FAULT 2 stores the 3rd latest fault code.
For the ABB event log and fault snapshot parameter group:
On ABB ACS580 Standard Control Program, two event logs store time-stamped information on the last 32 fault recordings (faults that tripped the drive or fault resets) and the last 32 warnings, pure events, or clearing entries.
On ABB ACS580 Standard Control Program, for each stored fault the control panel shows the fault code, time, and values of nine parameters (actual signals and status words) stored at the time of the fault; the values for the latest fault are in parameters 05.80…05.88.
On ABB ACS580 Standard Control Program, parameter 05.80 Motor speed at fault displays 24.02 Used speed feedback (-30000.00…30000.00 rpm, 10 = 1 rpm) at which the fault occurred.
On ABB ACS580 Standard Control Program, parameter 05.82 DC voltage at fault shows a copy of parameter 01.11 DC voltage (0.00…2000.00 V, 10 = 1 V) and 05.83 shows Motor current at the occurrence of the latest fault.
On ABB ACS580 Standard Control Program, parameter 05.84 Motor torque at fault shows a copy of 01.10 Motor torque (-1600.0…1600.0%, 1 = 1%) and 05.85 shows Main status word at the occurrence of the latest fault.
On ABB ACS580 Standard Control Program, parameter 05.87 Inverter temperature at fault shows a copy of parameter 05.11 Inverter temperature (drive temperature in °C, scaling 1 = 1 °C) at the occurrence of the latest fault.
Write down both the latest fault snapshot and the preceding fault codes so you can see whether repeated resets masked an earlier root event.
Read the Yaskawa and Danfoss fault trace and alarm logs
For the Yaskawa fault trace and history monitor parameters:
On Yaskawa GPD 515/G5 (TM 4557), in the Fault Trace monitor table, registers 080h (U2-01 Current Fault) and 081h (U2-02 Last Fault) record the code of the current fault (1) and second-to-current fault (1).
On Yaskawa GPD 515/G5, in the Fault Trace monitor table, parameter U2-03 (082h) records Frequency Reference at the time of the current fault and parameter U2-04 (083h) records Output Frequency at the time of current fault (400.0 Hz maximum).
On Yaskawa GPD 515/G5, in the Fault Trace monitor table, parameter U2-05 records Output Current at the time of current fault (drive rating /8192) and parameter U2-06 records Motor Speed at the time of current fault (in 0.1 Hz).
On Yaskawa GPD 515/G5, in the Fault Trace monitor table, parameter U2-07 records Output Voltage at Fault (in 0.1 V), parameter U2-08 records DC Bus Voltage at Fault (in 1 V), and parameter U2-09 records Output kWatts at Fault.
On Yaskawa GPD 515/G5, in the monitor table, parameter U2-14 records Elapsed Time at the time of fault (in hrs.), whereas Fault History parameters U3-01 (Last Fault, 1) and U3-02 (Fault Message 2) store the most recent fault codes.
For the Yaskawa peak-hold current and frequency monitors:
On Yaskawa GA800 drives, the peak hold current value is held during baseblock (when stopped) and when the power supply is restarted.
On Yaskawa GA800 drives, setting o4-26 [Peak Hold Initialization Selection] to 1 resets the monitor values of U4-87 [PeakHold Current 2], U4-88 [PeakHold Output Freq 2], and U4-89 [PeakHold Cumulative Ope Time].
For the Danfoss alarm log and fault log array parameters:
On Danfoss VLT AutomationDrive, pressing [Alarm Log] on the Local Control Panel shows an alarm list of the 5 latest alarms (numbered A1–A5), and pressing [OK] obtains more details about an alarm.
On Danfoss VLT AutomationDrive, parameter group 15-3* Alarm Log uses array parameters where up to 10 fault logs can be viewed, with 0 as the most recent logged data and 9 as the oldest.
On Danfoss VLT AutomationDrive, parameter 40-44 Fault Log: DC Link Voltage (default value 0V, conversion index 0) is a readout Array [10] parameter used to view the DC-link voltage when the logged event occurred.
On Danfoss VLT AutomationDrive FC 360, parameter 15-30 Alarm Log: Error Code is an Array [10] parameter (default value 0, range 0–255, 1 setup, conversion index 0) used to view the error code from logged events.
On Danfoss VLT AutomationDrive, when a Trip lock occurs, an alarm occurred and the motor is stopped; once the cause of the alarm is cleared, power must be cycled to the adjustable frequency drive before resetting manually.
When a cabinet contains multiple drives from different series, label each diagnostic entry with the drive tag and exact parameter group before comparing values across the lineup.

Label each drive tag and parameter group when capturing fault logs across multi-drive control cabinets.
Capture the pre-reset diagnostic worksheet
Use this pre-reset worksheet at the cabinet door before clearing the active trip:
| Diagnostic item | Information to record before reset |
|---|---|
| Active fault entry | Record the displayed fault code, alarm number, and fault text before pressing Reset. |
| Frozen operating snapshot | Record the logged motor speed, output frequency, intermediate circuit voltage, motor current, and motor torque at the moment of trip. |
| Drive status and digital inputs | Record the hexadecimal drive status word and the active digital input states captured with the latest fault. |
| Prior fault sequence | Record the previous fault codes in chronological order before power cycling the cabinet. |
| Thermal and elapsed-time readout | Record the inverter temperature, elapsed operating hours at fault, and peak-hold current readout where supported. |
Swipe or scroll horizontally to see all columns.
Isolate power and discharge capacitors before opening the enclosure
Recording keypad parameters is an external observation step; once you transition to terminal inspection or wiring checks, follow these workplace deenergizing and capacitor-discharge rules:
Under OSHA work practices, live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional hazards or is infeasible.
Under OSHA work practices, control circuit devices such as push buttons, selector switches, and interlocks may not be used as the sole means for deenergizing circuits or equipment.
Under OSHA work practices, stored electric energy which might endanger personnel shall be released, and capacitors shall be discharged and high capacitance elements short-circuited and grounded.
Under paragraph (3) Purpose of the OSHA lockout/tagout standard, employers are required to establish a program and utilize procedures for affixing appropriate lockout devices or tagout devices to energy isolating devices.
On ABB ACS580-01 drives, after disconnecting power from the drive, personnel must always wait 5 minutes to let the intermediate circuit capacitors discharge before continuing.
After completing lockout and verifying that stored energy has dissipated, inspect the power and control terminations using our VFD wiring basics guide.

Lock out the upstream energy isolating device and wait for capacitor discharge before internal inspection.
Prepare your VFD troubleshooting and replacement enquiry
If the captured fault log points to an internal hardware fault or you need a compatible replacement unit, include these items in your enquiry alongside our VFD replacement checklist:
| Enquiry item | Details to include |
|---|---|
| Fault code and alarm log | Provide the active fault code, alarm number, and previous fault sequence recorded before reset. |
| DC bus voltage at trip | Provide the logged intermediate circuit or DC bus voltage captured at the moment of the fault. |
| Output current and speed at trip | Provide the logged motor current, output frequency, motor speed, and torque snapshot at trip. |
| Drive and motor identification | Provide the drive part number, motor nameplate data, and application load type. |
| Cabinet and wiring context | Note recent wiring changes, reset source, and whether power was cycled before recording the log. |
Swipe or scroll horizontally to see all columns.
Discuss your variable frequency drive sourcing requirements with us. Include the recorded fault code, DC bus voltage, output current at trip, and drive nameplate details via WhatsApp or our contact page.
Frequently asked questions
Why does the live keypad screen clear the running output values right after a fault?
On Danfoss VLT AutomationDrive, when a Trip occurs (such as Earth Fault [A14] Auto Remote Trip), the live Status screen displays 0.0Hz, 0.00A, and 0.000kW.
What happens to the ABB assistant panel fault logger when power is turned off?
In ABB ACS550-01/U1 Fault Logger mode, the user can view the drive fault history of maximum ten faults, and after a power off, only the three latest faults are kept in the memory.
In ABB ACS550-01/U1 Fault Logger mode, the user can see the details of the three latest faults, and after a power off, the details of only the most recent fault is kept in the memory.
Can a keypad stop button or selector switch serve as the sole means of deenergizing a VFD?
Under OSHA work practices, control circuit devices such as push buttons, selector switches, and interlocks may not be used as the sole means for deenergizing circuits or equipment.
Which fault log values should be included when requesting VFD troubleshooting or replacement support?
Include the active fault code, the logged DC bus voltage at trip, and the logged output current at trip along with the drive and motor nameplate data.
Sources
- ABB — User Manual for Variable Frequency Drives
- ABB — Machinery Drive User Manual
- ABB — Standard Control Program Firmware Manual
- ABB — Hardware Manual for Variable Frequency Drives
- Yaskawa — Modbus Plus Technical Manual
- Yaskawa — General Purpose Drive Technical Manual
- Yaskawa — Supplemental Technical Manual for AC Drives
- Danfoss — Programming Guide for VLT AutomationDrive
- Danfoss — Instruction Manual for VLT AutomationDrive
- KEB America — VFD Protection Functions Introductory Guide
- US Government Publishing Office — Electrical Safety-Related Work Practices and Hazardous Energy Control