Technical guide
Inverter Duty Motor Insulation and Bearing Current
Verify inverter duty motor winding insulation withstand, partial-discharge limits, output filter rules, and VFD shaft grounding ring or insulated bearing protection.

Jack Dean writes practical VFD selection, wiring, replacement and power-quality guides using current manufacturer documentation and explicit procurement checks.
Author profileStart your inverter duty motor selection or replacement review by verifying the stator winding insulation rating and the bearing current protection arrangement against your drive supply voltage, cable route, and driven load. When comparing proposals across the inverter duty motor market, request the exact winding insulation clause, peak voltage and rise-time rating, and VFD shaft grounding ring or insulated-bearing configuration on the quotation rather than relying on a catalog label alone. Bring your motor nameplate and operating requirements to your industrial motors enquiry.
Check the definite-purpose inverter-fed motor scope and operating limits
We review each motor nameplate and quotation against the scope, service factor, voltage tolerance, excess current capability, and starting rules for definite-purpose inverter-fed polyphase motors:
In ANSI/NEMA MG1 Section IV Part 31, Section IV Part 31 applies to definite purpose polyphase squirrel cage induction motors rated 5000 horsepower or less at 7200 volts or less, intended for use with adjustable voltage and adjustable frequency controls, commonly referred to as inverters.
Under Clause 31.3.7 of ANSI/NEMA MG1 Part 31, a motor covered by Part 31 shall have a service factor of 1.0.
Under Clause 31.4.3.2 of ANSI/NEMA MG1 Part 31, definite purpose inverter-fed motors shall operate successfully throughout their defined speed range when the applied fundamental voltage does not vary from the rated value at any operating point by more than ±10%.
Under Clause 31.4.3.3 of ANSI/NEMA MG1 Part 31, definite purpose inverter-fed motors shall be capable of withstanding an occasional excess current for a period of not less than 1 minute when initially at normal operating temperature, at 110 percent of base current with a time interval of ≥9 minutes between overloads.
Under Clause 31.4.3.1 of ANSI/NEMA MG1 Part 31, while definite purpose motors may be capable of being started across-the-line, locked-rotor current at line frequency and voltage may exceed that for general purpose motors, and for large motors the stator end-winding support may be inadequate.
In the U.S. Department of Energy Motor Systems Tip Sheet, while a premium efficiency, totally enclosed fan-cooled 10-hp motor may be capable of a 10:1 constant-torque speed range, an inverter-duty motor is capable of providing full-rated torque at zero speed as well as operating well over its base speed.
Record the required constant-torque speed range, continuous load current, and starting method on your specification sheet before comparing candidate motor frames.
Compare reflected-wave voltage stress and stator winding insulation standards
Compare how cable impedance mismatch, fast-switching pulse rise times, and winding temperature affect stator winding insulation systems:
In the U.S. Department of Energy Motor Systems Tip Sheet, when motor impedance is greater than the impedance of the conductor cable between the motor and the drive, the voltage waveform reflects at the motor terminals to create a standing wave, and voltage spikes have occurred with peak values as high as 2,150 volts (V) in a 480-V system operating at 10% overvoltage.
In the U.S. Department of Energy Motor Systems Tip Sheet, NEMA MG 1-2011, Part 30 provides performance standards for general-purpose motors used with VFDs: when operated under usual service conditions, no significant reduction in service life should occur if the peak voltage at the motor terminals is limited to 1,000 V and rise times equal and exceed 2 microseconds.
In the U.S. Department of Energy Motor Systems Tip Sheet, NEMA MG 1-2011, Part 31 specifies that insulation systems for definite-purpose, low-voltage (≤ 600 V) inverter-duty motors should be designed to withstand an upper limit of 3.1 times the motor's rated line-to-line voltage, which is equivalent to an upper limit of 1,426 peak volts at the motor terminals for a motor rated at 460 V, with rise times that must equal or exceed 0.1 microsecond.
In the U.S. Department of Energy Motor Systems Tip Sheet, the insulation system on a 208/230-V motor is identical to that of a 460-V motor, so voltage spikes produced by inverters on 208- or 230-V systems are unlikely to cause insulation damage at any cable length or drive carrier frequency.
For definite-purpose inverter-fed motor withstand and partial-discharge limits:
Under Clause 31.4.4.2 of ANSI/NEMA MG1 Part 31, when operated under usual service conditions where inverter input nominal voltage does not exceed rated motor voltage, stator winding insulation systems for definite purpose inverter-fed motors with a base rating less than or equal to 600 volts shall be designed to operate at a single amplitude zero-to-peak line-to-line withstand voltage Vpeak ≤ 1.1 * 2 * √2 * Vrated ≤ 3.1 * Vrated at the motor terminals with Rise time ≥ 0.1 μs.
Under Clause 31.4.4.2 of ANSI/NEMA MG1 Part 31, stator winding insulation systems for definite purpose inverter-fed motors with a base rating less than or equal to 600 volts shall also be designed to operate partial discharge (PD) free at a single amplitude zero-to-peak line-to-line PD-free voltage at the motor terminals within ≤ 1.1 * 1.5 * √2 * Vrated ≤ 2.23 * Vrated with Rise time ≥ 0.1 μs.
In Table 31-3 of ANSI/NEMA MG1 Part 31, for a rated line-to-line voltage Vrated of 230 V, the minimum acceptable single amplitude zero-to-peak line-to-line withstand voltage (Vwithstand) measured at the motor terminals is 716 V and the PD-free voltage (VPD-free) is 513 V.
In Table 31-3 of ANSI/NEMA MG1 Part 31, for a rated line-to-line voltage Vrated of 460 V, the minimum acceptable single amplitude zero-to-peak line-to-line withstand voltage (Vwithstand) measured at the motor terminals is 1431 V and the PD-free voltage (VPD-free) is 1025 V.
In Table 31-3 of ANSI/NEMA MG1 Part 31, for a rated line-to-line voltage Vrated of 575 V, the minimum acceptable single amplitude zero-to-peak line-to-line withstand voltage (Vwithstand) measured at the motor terminals is 1789 V and the PD-free voltage (VPD-free) is 1281 V.
In ANSI/NEMA MG1, to demonstrate the ability to operate PD free at the PD-free voltage, the type test procedure in Clause 11 of IEC 60034-18-41 Edition 1 shall be used on representative samples when the stator winding insulation system is initially qualified, and is not intended to be a required routine test for each motor produced.
In Table 31-4 of ANSI/NEMA MG1 Part 31, for sinusoidal or impulse voltage with a fall time ≥10 µS for the trailing edge, the peak-to-peak test voltage for Vrated = 460 V with PD-free voltage Vpeak = 1025 V is 2563 V for the phase/phase PD test (multiplied by 2.5) and 1794 V for the phase/ground PD test (multiplied by 0.7).
In ANSI/NEMA MG1, when operated under usual service conditions 31.1.2 where inverter input nominal voltage does not exceed rated motor voltage, stator winding insulation systems for definite purpose inverter-fed motors with a base rating above 600 volts shall be designed to operate at a single amplitude zero-to-peak line-to-line voltage ≤ 2.04 * Vrated at the motor terminals with Rise time ≥ 1 μS.
Under Clause 31.4.4.4 of ANSI/NEMA MG1 Part 31, neutral shift in some current-source inverters can be as high as 2.3 per unit, resulting in motor line-to-ground voltages of up to 3.3 per unit (3.3 times the crest of the nominal sinusoidal line-to-ground voltage), whereas in a typical voltage-source inverter the line-to-ground voltage magnitude can be as high as √3 times the crest of the nominal sinusoidal line-to-ground voltage.
For random-wound and form-wound stator winding insulation qualification and temperature effects on partial discharge:
In the Qualitrol-Iris Power paper on IEC winding insulation standards, IEC 60034-18-41 covers Type I insulation systems (typically random-wound stators, which usually apply to motors rated < 1,000 V), while IEC 60034-18-42 covers Type II insulation systems (typically form-wound coils).
In the Qualitrol-Iris Power paper on IEC winding insulation standards, PWM inverter surges can be as much as three or four times the rated rms phase-to-ground voltage with a risetime as short as 50 ns, resulting in a non-uniform distribution of the impulse voltage with the turns in the first coil seeing much higher stress, and if electrical stress in small air gaps exceeds the dielectric breakdown strength of air (about 3 kV/mm for uniform fields), a partial discharge (PD) occurs.
In the Qualitrol-Iris Power paper on IEC winding insulation standards, for Type I systems in IEC 60034-18-41, impulse risetime and magnitude are classified into four categories—benign, moderate, severe, or extreme—and for qualification as a Type I insulation system for an inverter duty application, the repetitive partial discharge inception voltage (RPDIV) measured after each aging cycle must remain above the levels shown in Table 1 plus a 30% safety factor.
In Table 2 of the Qualitrol-Iris Power paper on IEC winding insulation standards, the example minimum zero-to-peak impulse RPDIV for a 460 v rated motor fed by a two-level converter is 1771 V (Benign 1.1), 2416 V (Moderate 1.5), 3221 V (Severe 2.0), and 4027 V (Extreme 2.5) phase-to-phase, and 1240 V, 1691 V, 2255 V, and 2818 V phase-to-ground or turn-to-turn.
In the GAMBICA and BEAMA Technical Guide, partial discharge (PD) inception voltage is influenced by temperature, and reports indicate that an increase in temperature of 80 K may reduce the PD inception voltage by approximately 10%.
In the GAMBICA and BEAMA Technical Guide, for the normal class B temperature rise (80 K), correction factors for temperature and first-coil voltage indicate a permissible terminal voltage peak of 1.3 kV with a rise time of 0.1 µs for a projected lifetime of 1013 pulses for standard motors from BEAMA manufacturers and supply voltages up to and including 500 V a.c. as shown by Curve A in Figure 21.
When reviewing motor datasheets with us, specify both the required peak withstand voltage and the partial-discharge-free voltage or stress category for the actual line voltage.

Inspect stator winding insulation documentation and phase-insulation specifications against the drive pulse rise time and peak terminal voltage.
Match motor insulation ratings to drive supply voltage, cable length, and output filters
Check how drive hardware manuals connect AC supply voltage, resistor braking duty, and motor insulation ratings to output filter and cable-length limits:
In the ABB ACS580-01 Hardware Manual, regardless of frequency, the drive output comprises pulses of approximately the drive DC bus voltage with a very short rise time, and the voltage peaks at the motor terminals are relative to the supply voltage of the drive, not to the drive output voltage.
In the ABB ACS580-01 Hardware Manual, du/dt filters protect the motor insulation system and reduce bearing currents, common mode filters mainly reduce bearing currents, and insulated N-end (non-drive end) bearings protect the motor bearings.
In the ABB ACS580-01 Hardware Manual, when the motor brakes machinery, the intermediate circuit DC voltage of the drive increases with an effect similar to the motor supply voltage increasing by up to 20 percent; for example, a 400 V AC line voltage application must be selected as if the drive were supplied with 480 V.
In the ABB ACS580-01 Hardware Manual requirements table for ABB random-wound M2_, M3_, and M4_ motors, the power and frame size columns are Pn < 100 kW and frame size < IEC 315 (Pn < 134 hp and frame size < NEMA 500), 100 kW ≤ Pn < 350 kW or IEC 315 ≤ frame size < IEC 400 (134 hp ≤ Pn < 469 hp or NEMA 500 ≤ frame size ≤ NEMA 580), and Pn ≥ 350 kW or frame size ≥ IEC 400 (Pn ≥ 469 hp or frame size > NEMA 580), requiring - / +N / + N + CMF respectively at Un ≤ 500 V with Standard insulation.
In the ABB ACS580-01 Hardware Manual Additional requirements for non-ABB high-output and IP23 motors table, for nominal AC supply voltage 420 V < Un < 500 V, a motor with Standard insulation (ÛLL = 1300 V) requires + du/dt + (N or CMF) for Pn < 100 kW or frame size < IEC 315 and + N + du/dt + CMF for 100 kW < Pn < 350 kW or IEC 315 < frame size < IEC 400, whereas a motor with Reinforced insulation (ÛLL = 1600 V, 0.2 microsecond rise time) requires + N or CMF.
In the ABB ACS580-01 Hardware Manual Additional requirements for non-ABB high-output and IP23 motors table, for 500 V < Un ≤ 600 V a motor with Reinforced insulation ÛLL = 1600 V requires + du/dt + (N or CMF) for Pn < 100 kW or frame size < IEC 315 and + N + du/dt + CMF for 100 kW < Pn < 350 kW or IEC 315 < frame size < IEC 400, whereas Reinforced insulation ÛLL = 1800 V requires + N or CMF for Pn < 100 kW or frame size < IEC 315 and + N + CMF for 100 kW < Pn < 350 kW or IEC 315 < frame size < IEC 400; for 600 V < Un ≤ 690 V, Reinforced insulation ÛLL = 2000 V with 0.3 microsecond rise time requires + N + CMF.
In the ABB ACS580-01 Hardware Manual, a sine filter also protects the motor insulation system, and the peak phase-to-phase voltage with a sine filter is approximately 1.5 · Un.
In the ABB ACS550-01/U1 User's Manual, for 500…600 V drives (ACS550-U1-XXXX-6), either the motor is a NEMA MG1 Part 31 motor that complies with NEMA MG1 Part 31 or a du/dt filter is used between the motor and drive.
In Table 5 of the Rockwell Automation PowerFlex 40P User Manual, maximum motor-cable-only length recommendations for reflected wave on 380-480V ratings across frequencies 2…16 kHz by motor insulation rating are 15 m (49 ft) for 1000 Vp-p, 40 m (131 ft) for 1200 Vp-p, and 170 m (558 ft) for 1600 Vp-p, while for 240V ratings reflected wave effects do not need to be considered.
When your motor cable route or insulation tier calls for output conditioning, use our VFD motor cable length checklist to record the installed run and compare reactor and filter options in our line reactor vs load reactor guide and power quality products catalog.

Match the drive supply voltage, braking duty, and motor insulation rating when selecting an output filter or reactor.
Understand bearing currents and select a VFD shaft grounding ring or insulated bearing
Distinguish sinusoidal magnetic dissymmetry, capacitive common-mode electrical discharge machining, and high-frequency circulating currents before specifying a VFD shaft grounding ring or insulated bearing:
Under Clause 31.4.4.3 of ANSI/NEMA MG1 Part 31, in larger frame size motors—usually 500 frame and larger—shaft end-to-end voltages may be present under sinusoidal operation due to magnetic dissymmetries, can be interrupted by insulating one of the bearings, and if the shaft voltage is larger than 300 millivolts peak when tested per IEEE 112, bearing insulation should be utilized.
Under Clause 31.4.4.3 of ANSI/NEMA MG1 Part 31, inverter-generated high-frequency common-mode voltage shifts the three-phase winding neutral potentials from ground and is capacitively coupled to the rotor in induction motors of all sizes, resulting in peak pulses as high as 10-40 volts from shaft to ground that can flow through either or both bearings.
Under Clause 31.4.4.3 of ANSI/NEMA MG1 Part 31, interrupting common-mode shaft-to-ground current by bearing insulation requires insulating both bearings, and insulating the motor bearings will not prevent the damage of other shaft connected equipment; alternative mitigations include changing drive topology, adding filters, improving system grounding, or using shaft grounding brushes.
In the ABB motor bearings technical white paper by Bevan Christiansen, the oil in bearing grease forms a film that acts as a dielectric until it breaks down, allowing shaft voltage to arc through the bearings—commonly referred to as electrical discharge machining (EDM)—producing micron-sized pitting called frosting and washboard-like ridges in the bearing raceway called fluting.
In the ABB motor bearings technical white paper by Bevan Christiansen, shaft-grounding rings contain multiple strands of electrically conductive fibers arranged inside a ring around the shaft and, unlike carbon brushes, can be mounted inside the motor for washdown duty and dirty duty motors, whereas grounding rings mounted externally tend to collect contaminants on their bristles.
In the ABB motor bearings technical white paper by Bevan Christiansen, ceramic bearings (with ceramic-coated balls) protect the bearings by preventing shaft current from flowing through the bearings to the motor, but because they do not remove current from the rotor, the current will seek a path to ground through attached equipment, and ceramic bearings are usually available only up to size 6311.
In the ABB motor bearings technical white paper by Bevan Christiansen, on motors larger than 100 horsepower, it is generally recommended that an insulated bearing be installed on the opposite end of the motor on which the shaft grounding device is installed, regardless of which style of shaft grounding is used.
In Electro Static Technology AEGIS shaft voltage guidance, in large motors with an output exceeding 100HP/75kW, the end-to-end shaft voltage is sufficiently high to drive a high-frequency circulating current through the bearings, whereas capacitive shaft voltage is present in all motors run by VFDs, so all motors on drives are susceptible to capacitive EDM current.
In Electro Static Technology AEGIS product specifications, AEGIS SGR is specified for motors under 500 HP/375 kW, while AEGIS PRO Series is specified for motors over 300 HP/225 kW.
On ABB Baldor-Reliance Shaft Grounded Motors, the motors feature Insulation Class H suitable for Inverter Duty per NEMA MG1 Part 31.4.4.2 and an internally mounted shaft grounding ring (-G suffix, power range 1 - 100Hp / 0.75 - 75 kW) or carbon brush (-BG suffix, power range 1 - 50Hp / 0.75 - 37 kW).
Tell us whether the motor drives a direct-coupled gearbox, pump, or encoder and whether washdown or dusty conditions require an internally mounted shaft grounding ring paired with an opposite-end insulated bearing.

Specify whether the application requires an internal or external shaft grounding ring and an opposite-end insulated bearing.
Prepare your inverter duty motor and bearing protection enquiry
When you request an industrial motor or motor-and-drive package quotation, include the items below so we can align the winding insulation tier, output filter, and bearing protection with your installation:
| Enquiry item | Details to include |
|---|---|
| Motor nameplate and frame | Provide the rated power, voltage, full-load current, speed, frame designation, mounting arrangement, and enclosure type. |
| Winding insulation specification | Specify the required standard clause, peak line-to-line voltage rating, minimum pulse rise time, or partial-discharge stress category. |
| Drive supply and braking duty | Record the drive nominal supply voltage, switching frequency, and whether resistor braking or regenerative operation is used. |
| Cable route and output filtering | Record the installed motor cable length and note any existing or planned output reactor, du/dt filter, sine filter, or common-mode filter. |
| Bearing protection and coupled load | Specify whether an internal or external VFD shaft grounding ring, opposite-end insulated bearing, or coupled gearbox and pump protection is required. |
Swipe or scroll horizontally to see all columns.
Discuss your industrial motors sourcing requirements or complete variable frequency drive packages with us. Send your motor nameplate, drive supply voltage, cable length, and bearing protection requirements via WhatsApp or our contact page.
Frequently asked questions
What service factor applies to a definite-purpose inverter-fed motor?
Under Clause 31.3.7 of ANSI/NEMA MG1 Part 31, a motor covered by Part 31 shall have a service factor of 1.0.
What are the minimum withstand and partial-discharge-free voltages in the definite-purpose motor table?
In Table 31-3 of ANSI/NEMA MG1 Part 31, for a rated line-to-line voltage Vrated of 460 V, the minimum acceptable single amplitude zero-to-peak line-to-line withstand voltage (Vwithstand) measured at the motor terminals is 1431 V and the PD-free voltage (VPD-free) is 1025 V.
When should an opposite-end insulated bearing be paired with a VFD shaft grounding ring?
In the ABB motor bearings technical white paper by Bevan Christiansen, on motors larger than 100 horsepower, it is generally recommended that an insulated bearing be installed on the opposite end of the motor on which the shaft grounding device is installed, regardless of which style of shaft grounding is used.
Why are ceramic bearings alone insufficient to protect coupled driven equipment?
In the ABB motor bearings technical white paper by Bevan Christiansen, ceramic bearings (with ceramic-coated balls) protect the bearings by preventing shaft current from flowing through the bearings to the motor, but because they do not remove current from the rotor, the current will seek a path to ground through attached equipment, and ceramic bearings are usually available only up to size 6311.
What details should be included when requesting an inverter duty motor quote?
Include the motor nameplate data, frame and mounting arrangement, drive supply voltage, motor cable length, required winding insulation standard, and preferred VFD shaft grounding ring or insulated-bearing configuration.
Sources
- NEMA — Definite Purpose Inverter-Fed Polyphase Motor Standard
- U.S. Department of Energy — Motor Systems Tip Sheet on Inverter-Duty Motors
- Qualitrol-Iris Power — IEC Standards for Variable Speed Drives and Motor Winding Insulation
- GAMBICA and BEAMA — Variable Speed Drives and Motors Technical Guide
- ABB — General Purpose Drives Hardware Manual
- ABB — User Manual for Variable Frequency Drives
- Rockwell Automation — Adjustable Frequency AC Drive User Manual
- ABB — Motor Bearings Protection Technical White Paper
- ABB Baldor-Reliance — Shaft Grounded Motors Technical Data
- Electro Static Technology — Shaft Voltage and Bearing Current Protection Guidance