VFDDistributor
Back to Learning Center

Technical guide

Line Reactor vs Load Reactor: Impedance and Placement

Compare VFD input and output reactor placement, interpret percent impedance, and check current ratings before choosing a reactor or dV/dt filter.

Line reactor versus load reactor cover with a three-phase reactor and position, current and impedance icons
Jack Dean

Jack Dean writes practical VFD selection, wiring, replacement and power-quality guides using current manufacturer documentation and explicit procurement checks.

Author profile

A line reactor connects between the supply and the VFD input; a load reactor connects between the VFD output and the motor. The first addresses input-side electrical conditions. The second addresses the drive-to-motor circuit, where the reactor must be suitable for the drive’s pulse-width-modulated (PWM) output.

For a line reactor vs load reactor comparison, start with the affected side of the drive, then compare the component’s current rating, impedance basis and permitted duty. A percentage stamped on a selection table becomes useful only when its voltage, frequency and current references are known.

Line reactor vs load reactor at a glance

Electrical position determines the job; the selected product’s ratings determine whether it can do that job. Some reactor families support both positions, while others require a separate output selection or derating.

Selection questionLine reactorLoad reactor
Where is it connected?In series with the supply, ahead of the VFD inputIn series between the VFD output and motor
What is the main objective?Add input impedance to moderate supply disturbances and reduce drive input-current distortionModerate PWM-related waveform effects in the motor circuit
Which operating conditions matter?Supply voltage/frequency, source conditions, existing impedance and drive loadingOutput current, PWM suitability, switching conditions, motor and cable
How is percent impedance selected?Use the input selection table and its current, voltage and frequency basisUse the output-specific instructions for that product family
What mistake changes the result?Adding only an input reactor when the requirement concerns motor-terminal voltageMoving an input-only part to the output without checking its PWM and thermal rating

Swipe or scroll horizontally to see all columns.

TCI’s Line and Load Reactors Basics describes the reactor as a series inductor. In a three-phase unit, an inductive winding is placed in each phase. If an equipment list simply calls for an inductor for a VFD, identify whether it means an AC input reactor, an AC output reactor or a DC-link choke before ordering: these positions are different parts of the drive circuit.

Three copper reactor windings with separate terminal lugs on a laminated steel core

Component illustration: the three winding assemblies make the phase structure visible. Line or load suitability comes from the component’s electrical ratings and application instructions.

Where each reactor goes

Place the reactor on the electrical side that matches the requirement. The line-side sequence is supply → line reactor → VFD. The load-side sequence is VFD → load reactor → motor. MTE’s RL Reactors Technical Reference Manual, July 2025 Rev.003, shows these arrangements in Figures 5-1 and 5-2 on printed page 39.

Two circuit paths: the line reactor is before the VFD, and the load reactor is after the VFD

Input and output applications shown separately. Each path locates the reactor relative to the VFD; the application determines which accessories are needed. Schematic, not to scale.

Electrical position and physical mounting location are separate decisions. Once the correct side is established, follow the selected reactor or filter’s mounting instructions, lead arrangement, ventilation and enclosure requirements. For example, MTE’s RL manual permits that family at either the drive or motor in an output application. That permission belongs to the specified product family.

If the objective concerns input harmonics, use the VFD harmonics and line reactor guide to assess the supply-side requirement. If it concerns the motor’s cable run or voltage waveform, assess the output circuit directly.

What does 3% or 5% impedance mean?

Percent impedance expresses the reactor’s inductive voltage drop relative to the circuit voltage at a defined current and frequency. It is a normalized rating, so the same inductance can have a different applied percentage when the current, voltage or frequency changes.

MTE’s Reactor %Z Impedance Derivation by Wayne Walcott gives this balanced three-phase relationship, using inductive reactance and neglecting winding resistance:

Z% = 100 × √3 × I × 2πfL / VLL

SymbolQuantity and unit
Z%Impedance expressed as a percentage, such as 5 for 5%
ICurrent reference used by the selection method, in amperes
fFundamental frequency, in hertz
LInductance of each phase winding, in henries
VLLLine-to-line RMS voltage, in volts

Swipe or scroll horizontally to see all columns.

Use the stated fundamental frequency for this calculation. The PWM carrier frequency is a separate output-duty consideration. Also preserve the manufacturer’s current convention: a table based on fundamental current and a thermal rating stated in RMS amperes answer different questions.

Why current oversizing changes the applied percentage

A larger ampere rating alone does not preserve the desired impedance. Compare the inductance and the reference current as well as the component’s ability to carry the load.

The MTE Solutions Catalog, printed page 6, gives a useful example: a reactor that provides 5% impedance at its rated current provides 3% when current falls to 60% of that value. At unchanged voltage and frequency, with substantially constant inductance:

Z%applied = Z%reference × Iactual / I reference = 5% × 0.60 = 3%.

This is why an ampacity substitution also needs an impedance check. A thermally acceptable component may provide a different electrical effect at the intended operating current.

Is 5% impedance a 5% reduction in drive voltage?

The voltage across the reactor and the reduction in voltage magnitude at the drive terminals are different quantities. Eaton makes this distinction in its technical explanation Does a 5% Reactor Cause a 5% Voltage Drop at My Drive? The drive-terminal result depends on the circuit and phase relationships.

For each phase, the inductive voltage magnitude is I × 2πfL; the reference phase voltage is VLL / √3. Include the reactor in the installation’s voltage-budget calculation, together with source and cable conditions, rather than subtracting its percentage label directly from the supply voltage.

Choosing between 3% and 5%

Choose the input impedance against the required conditioning and available voltage margin. MTE’s RL selection guide lists 3% and 5% options and associates the higher impedance with greater input harmonic-current reduction. That selection still depends on the application and existing impedance.

Output selection needs its own table. For example, MTE’s RLW catalog recommends a maximum 1.5% output impedance, while the RL family has different selection guidance. Preserve the family name and input/output application whenever you compare percentages.

VFD line reactor sizing: checks in the right order

Select a current-and-inductance combination from the manufacturer’s table, then check duty and installation conditions. Motor horsepower alone leaves several of these checks unresolved.

  1. Identify the intended side and objective. Record input conditioning or output waveform requirements, and identify any existing DC choke, AC reactor or filter.
  2. Use the table’s current basis. Obtain drive input current, drive output current and motor full-load amperes. MTE’s RL guide correlates selection with motor FLA, voltage, frequency and phase count; follow the convention of the actual family being selected.
  3. Match voltage, frequency and impedance. Keep the reference conditions beside the percentage. Check the effect at the expected operating current as well as the full-load condition.
  4. Check overload and waveform duty. For an output reactor, verify permitted PWM service and switching conditions. HPS’s Load Reactor Applications explains that some input-reactor products require derating or a different part number on the output.
  5. Check the installed environment. Apply the selected manual’s ambient-temperature and altitude limits or derating curves. Confirm enclosure, mounting space and cooling provisions before accepting the panel layout.
Unwired reactor and VFD mounted on an electrical enclosure backplate with cable ducts beside them

Panel-layout illustration: mounting feet, cable-duct space and the area around the reactor all affect panel integration. Use the selected equipment’s clearance and thermal requirements when arranging the enclosure.

For a replacement or panel quotation, compare the mounting work, enclosure space, cooling provisions and cable terminations as well as the reactor itself. These installation requirements can change even when two proposals list the same nominal current and impedance.

Load reactor vs dV/dt filter: which output device fits?

Choose against the required motor-side waveform result. A load reactor adds series inductance. A dedicated dV/dt filter is designed to control the fast voltage transitions reaching the motor within its specified operating conditions. Schneider Electric’s FAQ FA115635 distinguishes the two functions; HPS describes a reactor with an RC snubber network as one output-filter implementation.

Decision pointLoad reactordV/dt filter
Function to evaluateSeries inductance and its effect on output current and PWM-related waveform behaviorSpecified control of voltage rise and motor-side high-frequency effects
Key product qualificationOutput/PWM rating, current, impedance, operating frequency and thermal limitsDrive compatibility, current, switching frequency, motor/cable conditions and stated waveform limits
When to retain this optionThe drive and reactor instructions support it for the actual motor circuitThe required motor-terminal waveform calls for the filter’s specified conditioning
What to compare before purchaseThe output-reactor application table and its conditionsThe filter’s performance specification and installation conditions

Swipe or scroll horizontally to see all columns.

If the selected reactor’s documented performance does not meet the required output-waveform limit, evaluate the appropriate output filter. Adding a line reactor on the input does not establish compliance with a motor-side waveform requirement. Equally, a cable-length number alone is insufficient to select the filter: the drive, motor, cable construction and switching conditions must match its application limits.

Motor cable entering a closed terminal box through a gland and following a supported tray toward a drive cabinet

Cable-route illustration: the installed path includes bends, supports and the final motor connection. Use the complete route and cable specification when checking output-device application limits.

The VFD motor cable length checklist helps organize the installed route and the limits in the exact drive documentation. Carry those inputs into the output-device comparison.

Common selection questions

Can the same reactor be used on either side of a VFD?

Yes, when its manufacturer approves it for both duties and the application matches its ratings. MTE RL is an example of a line/load family. Verify the particular part’s current, inductance, voltage and PWM conditions; its role still follows the side where it is connected.

Does a built-in DC choke eliminate the need for an AC line reactor?

Assess the existing drive design and supply-side objective together. A DC-link choke is located inside the DC circuit; an AC line reactor is ahead of the input. Identify what conditioning the drive already includes and follow its input-power guidance when deciding whether additional AC impedance is needed.

Can a line reactor replace a load reactor or output filter?

An input-mounted reactor addresses the supply-to-drive circuit. A motor-side requirement needs an output-side assessment. If a dual-rated reactor is moved to the output, check its output selection and mounting requirements for that application.

Compare accessories for your installation

Explore power-quality products for VFD installations to compare reactor and filter categories. For an enquiry, include the harmonic requirement, installed motor cable length and desired impedance percentage, together with the drive model, supply voltage/frequency, drive currents, motor FLA and existing choke or reactor. Include any specified motor-side waveform limit when comparing output devices.

Discuss reactor or filter sourcing on WhatsApp. These details give the enquiry a clear electrical position, operating basis and selection objective.

Technical references

  • MTE, RL Reactors Technical Reference Manual, July 2025 Rev.003: printed pages 5–8 for ratings, application and selection; page 39, Figures 5-1 and 5-2, for placement.
  • MTE, Reactor %Z Impedance Derivation, Wayne Walcott, page 1: three-phase equation and reference quantities.
  • MTE, Solutions Catalog, printed page 6: current-scaling example; RLW selection notes on physical PDF page 16: output-impedance recommendation.
  • TCI, Line and Load Reactors Basics, Josh Haase, pages 1–2: series-inductor function and input/output roles.
  • Eaton, Does a 5% Reactor Cause a 5% Voltage Drop at My Drive?: distinction between reactor drop and drive-terminal voltage reduction.
  • Schneider Electric, FAQ FA115635, Are Output Filters and Line Reactors the Same on VFDs?, updated April 17, 2026: reactor/filter distinction.
  • Hammond Power Solutions, Load Reactor Applications: output suitability and reactor-plus-RC filter example.

WhatsApp

Send this page with the details already filled in.

We include this page, your selected model or specifications, and a reference. You only add quantity and destination before sending.

Ask about this page on WhatsApp